Why Ac Calculated in Tons

Why AC appraised in Tons, Not in kW?
AC (Air-conditions and Refrigeration are constantly appraised in Tons.
Aeration and cooling systems are constantly evaluated in Tons capacityinstead of kW since Air conditioners are planned on the premise of amount of warmth expulsion from room, corridor or particular region. Amount of warmth is termed in Tons implies if a ventilation system can uproot 1000 kilocalories of warmth or 4120 kilojoules or 12000 BTU of warmth in an hour that AC evaluated as 1 Ton of AC since 1000 Kilocalories or 4120 kilojoules or 12000 BTU equivalent to one Ton of warmth. Additionally, this is the same case for cooler and icebox i.e. refrigeration framework.
Great to know:
BTU = British warm unit. An estimation of warmth, particularly, the measure of warmth expected to raise the temperature of a pound of water by 1°F.
Meaning of Ton
A Ton of refrigeration (RT) is roughly equal to 12,000 BTU/h or 3,516.8528 W or 4.7142Hp.
A Ton of refrigeration (RT) is a unit of force used to portray the warmth extraction capacity of ventilating and refrigeration types of gear. It is characterized as the warmth of combination consumed by dissolving 1 short ton of unadulterated ice at 0 °C (32 °F) in 24 hours.
What number of kW and HP are there in 1 Ton?
1 Ton = 3.5168525 kW = 4.714Hp
Clarification
1 Ton = 12,000 BTU/h
1 Watt = 3.412141633 BTU/h
1 Ton = 12,000/3.412141633 = 3,516.8528 Watts = 3.5168528 kW.
1 Ton = 3,516.8528 Watts = 3.516 kW.
Too
1 Ton = 3,516.8528W/746 = 4.7142798928 Hp →→→ (1 Hp = 746 Watts)
1 Ton = 4.714 Hp
How to change over Ton to Kw and the other way around?
One RT(Refrigeration Ton) = 3.5168528 kW…
1 RT = 3.5168528 kW
1 kW = 0.284345 RT(Refrigeration Ton)
1 kW = 0.28434517 RT
Thus,
The force P in kW = Power P in RT (Refrigeration Ton) times 3.5168528… .
P(kW) = P(RT) × 3.5168528
Case
Change over 3 Ton AC into kW i.e. Change over 3 RT to kW.
Arrangement:
P(kW) = 3 RT × 3.5168528
P(kW) = 10.55 kW
3 Ton AC = 10.55 kW
The amount Current in Ampere will a 2 Tons AC attract Single Phase and Three Phase System?
Assume, There are 230V and Power factor = Cosθ = 0.95 in Single Phase AC framework…
1 Ton = 3,516.8528 Watts = 3.516 kW.
2 Ton = 2 x 3.516 kW = 7.032kW = 7032W
Power in a Single Phase AC System
P = VxI Cosθ and current…
I = P/(V x Cosθ)… .. Where Cosθ = Power factor
I = 7032W/(230V x .95)
I = 32.18 A
In this manner, a 2 Ton AC (Air-condition in Single Phase AC framework will take 31.18 Ampere Current
Andin Three Phase System
Assume, There are 440V and Power factor = Cosθ = 0.85 in Three Phase AC framework…
Power in a Three Phase AC System
P =√3 x VLxIL Cosθ and current… .
I = P/( √3xVxCosθ)
I = 7032W/(1.732 x 440V x .85) Where Cosθ = Power factor and √3 = 1.732
I = 10.855 A
In this manner, a 2 Ton AC (Air-condition in Three Phase AC framework will take 10.855 Ampere Current
Great to Know:This is just count taking into account Electrical recipes. In genuine, Air conditioner current depends a ton on working conditions, for example, surrounding temperature, refrigerant weight, Energy Efficiency Ratio (EER) and so on for case, if EER is 6, then info power for 2 Tons Air conditioner is 24000BTU/6 = 4000 watts..
On the off chance that this is a 230 volt framework, then ventilation system load current would be = 4000/(230x.95) = 18.5 A
For More detail… Check the Air conditioner Name plate rating.
Another comparative rating is Coefficient of force (COP) which is the yield power in watts isolated by info power, so with a COP = 1.8, for case, information power for 2 Tons Air conditioner is 7032W/1.8 = 3906 watts. Presently you can discover current by utilizing the above strategy which is equivalent to 18A approx.
What number of 2 Ton A.C (Air conditioner) would I be able to keep running on a 25 kVA Generator?
2 Ton = 2 x 3.516 kW = 7.032kW = 7032W
The Efficiency of Utility Power Generator is 90% roughly.
Effectiveness of Generator = 25kVA x (90/100) = 22.5kVA
Presently the Number of 2 Ton AC (Air conditioners) which you can keep running on a 25 kVA Generator easily..
22.5kVA/7032W
= 3
So you can run Three Air conditioners of 2 Tons each on a 25kVA Generator.
What is the suitable rating of MCB for 2 Ton and 1 Ton AC (Air conditioner) and why?
As we have ascertained the heap current for 2 Ton AC Air conditioner…
Ascertained Current for 2 Ton A.C = I = 32.18 A
Presently 40A Class "C" MCB (smaller than expected electrical switch) would be suitable for 2 Ton AC (aerate and cool) on the grounds that in beginning time it takes more present of the full load current
What's more, 20 A Class "C" MCB would be better for 1 Ton AC (cool)
Great to Know:
Class "'C' Type MCBs
Class "C" Type MCBs are suitable for establishments with high inrush of current at the beginning exchanging time. as it were, hardware and gadgets having inductive loads, for example, aeration and cooling systems.

Comments

Popular posts from this blog

Poomully Mana- Mana for Ayurveda- An Overview

1. Tell us a brief history of Poomully Mana family ? The Poomully Namboothiri family, whose ancestral home was known by the name “Poomully Mana,” resided in Urakam of Peruvanam village in the interiors of Kerala. This family lived in an era that dates back by about 900 years. They built the original Ammathiruvadi Temple and left all their ancestral wealth to the Goddess and its administration to the Kingdom of Kochi. The family then relocated to Peringode (present-day Palakkad).  In the 'Aithihyamala' (a collection of centuries-old stories from Kerala, covering a vast spectrum of lives, famous people and events), Poomully Mana features as one of the families that had a glorious history. The members of Poomully Mana were famous Ayurvedic exponents and practitioners of the Rig Veda, Yoga, Kalaripayattu (a form of martial art), music and other cultural arts. Some of the better known members are the Late Sri Poomully Narayanan Namboodirippad (father of Aaramthampu...

Do I require a mortgage Broker?

Mortgage merchants can scour the business sector for you, searching for the right arrangement to suit your circumstance. They are additionally especially helpful in the event that you are in an unordinary position. Who can profit by utilizing a mortgage agent? Anybody getting a mortgage. It can be especially useful if: you depend on unpredictable independent income you are raising a mortgage on a second property to pay the store on the first you require a spanning credit What are the benefits of having one on my side? they know the business sector well and are up to speed with the most recent arrangements they know which moneylenders are alright with unordinary circumstances will offer exhortation and direction all through the procedure, will likewise go about as your backer with the mortgage moneylenders, making it less upsetting they can likewise at times get great arrangements, superior to anything you could get going direct to the moneylender What to keep an e...

Plumbing and Electrical- DIY

The law is highly contrasting with regards to chipping away at the electrical and plumbing frameworks in your home. On the off chance that it's much past changing a light or a tap washer, you will presumably need to get the significant authorized tradesperson onto it, if all else fails call a tradie. The accompanying data is a general diagram of only a percentage of the laws and regulations you should know about before endeavoring any work on the electrical and plumbing frameworks in and around your home. Try not to be tricked by the variety of electrical and plumbing treats in the handyman stores. You don't should be authorized to purchase them, yet you unquestionably should be authorized to introduce the greater part of them. While revamping discussions abound with angry rages from DIYers who say they could capability lay links and introduce pipework themselves, the dangers of doing as such are incredible. The principal thing to acknowledge is that there is ...